Other Tests (Part 1)

Other Testing Services Within the Scope of the Laboratory

Different tests are applied for various types of glass, insulating glass units, and their components. These include: (1) Dew point test, (2) Fogging test, (3) Tensile test, (4) U-value measurement, (5) g-value measurement, (6) Calcium chloride (CaCl2) test, (7) Calcium oxide (CaO) test, (8) Measurement of glass components, (9) Homogeneity measurement, (10) Shore-A hardness measurement, (11) Measurement of butyl application quantity, (12) Flatness and bow measurement, (13) Local bow measurement, and (14) Toughened glass identification tests. Information regarding these tests is provided below. Please contact our sales department for detailed questions.


TS EN 1279-2 Annex-A Insulating Glass Units – Dew Point Test


PRODUCT
Insulating glass unit (IGU) – With or without desiccant

TEST MATERIAL / COMPONENT
Insulating glass unit (IGU) – With or without desiccant

PURPOSE OF THE TEST
The condensation temperature of water or any organic volatile vapor inside the IGU is measured.

TEST DESCRIPTION
Conducted to determine whether water or any organic volatile vapor is present within the IGU.

REFERENCE TEST STANDARD
TS EN 1279-2 Annex-A

INTERNAL TEST METHOD NO
DY.(A)

TEST REPORT
One test (performance assessment) report and one report summary document will be provided.

SAMPLE INFORMATION FORM NO
NBF.1279.2

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
Laboratory

TÜRKAK ACCREDITATION
Yes (AB-0411-T)

NOTIFIED BODY SCOPE
This test is performed within the scope of the notified body according to the Construction Products Regulation (305/2011/EU) only for insulating glass units that do not contain desiccant. This test is a useful quality control test for insulating glass units containing desiccant as well, because even for insulating glass units containing desiccant, the dew point temperature must be lower than the temperature specified in the standard. Otherwise, the moisture penetration index may appear as less than zero (0).

RECOMMENDED TEST FREQUENCY
Please contact the sales department.


TS EN 1279-4 Annex-C Insulating Glass Units – Fogging Test

PRODUCT
Insulating glass unit

TEST MATERIAL / COMPONENT
Insulating glass unit

PURPOSE OF THE TEST
To check whether fogging occurs within the cavity of the insulating glass unit.

TEST DESCRIPTION
Checks whether fogging is present inside the cavity of the insulating glass unit.

REFERENCE TEST STANDARD
TS 3539-6 EN 1279-6 4 Annex-C

INTERNAL TEST METHOD NO
DY.04

TEST REPORT
One test (performance evaluation) report will be issued.

SAMPLE INFORMATION FORM NO
NBF.1279.2

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
Laboratory

TÜRKAK ACCREDITATION
No

NOTIFIED BODY SCOPE
This test is not conducted within the scope of the notified body under the Construction Products Regulation (305/2011/EU). It is a useful test for the quality control of glass units. It should definitely be performed at least once, especially when sealants or spacer bars are changed.

RECOMMENDED TEST FREQUENCY
Please contact the sales department.


TS EN 1279-4 Annex-A Outer Edge Sealants – Adhesion Test

PRODUCT
Insulating glass unit outer edge sealants

TEST MATERIAL / COMPONENT
Outer edge sealants and structural glass facade bonding materials.

PURPOSE OF THE TEST
To measure the bonding quality of outer edge sealants and structural glass facade bonding materials using a TIME tensile-compression testing machine.

TEST DESCRIPTION
Tensile strength (adhesion durability) of outer edge sealants and structural glass facade bonding materials is determined after curing and water immersion.

REFERENCE TEST STANDARD
TS EN 1279-4 Annex-A (A simplified version of this test is also known as Dow Corning's "H-Piece" test.)

INTERNAL TEST METHOD NO
DY.14

TEST REPORT
One test (performance assessment) report will be provided.

SAMPLE INFORMATION FORM NO
NBF.1279.4(A)

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
Laboratory

TÜRKAK ACCREDITATION
No

NOTIFIED BODY SCOPE
This test is not conducted within the scope of the notified body under the Construction Products Regulation (305/2011/EU). It is a useful test for the quality control of glass units, and particularly of outer edge sealants.

RECOMMENDED TEST FREQUENCY
Please contact the sales department.


TS EN 675-SBG Insulating Glass Unit – Determination of Thermal Transmittance (U-Value)

PRODUCT
Insulating glass unit

TEST MATERIAL / COMPONENT
Insulating glass unit

PURPOSE OF THE TEST
Thermal transmittance is measured experimentally using a heat flow meter and a heating cabinet.

TEST DESCRIPTION
The thermal transmittance of the insulating glass unit used is measured using a Testo 635 and a heating cabinet. The obtained value is compared with the calculated value or the value specified in the technical product specification. Compliance is thus determined; however, the test has not been validated, the test results have not been verified, and the test results may not provide consistent and reliable findings. Measurements are limited to the measuring capabilities of the test setup. Please consult the laboratory for detailed information.

REFERENCE TEST STANDARD
Internal method (TS EN 675-SBG)

INTERNAL TEST METHOD NO
DY.15

TEST REPORT
One test (performance evaluation) report will be issued.

SAMPLE INFORMATION FORM NO
NBF.673

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
Laboratory

TÜRKAK ACCREDITATION
No

NOTIFIED BODY SCOPE
This test is not conducted within the scope of the notified body under the Construction Products Regulation (305/2011/EU). This test is useful for measuring the thermal transmittance of insulating glass units, but more specifically for comparing the thermal transmittance of multiple insulating glass units against a reference unit.

RECOMMENDED TEST FREQUENCY
Please contact the sales department.


TS EN 410-SBG Insulating Glass Unit – Determination of Luminous Characteristics and Solar Heat Gain Coefficient (g-Value)

PRODUCT
Insulating glass unit

TEST MATERIAL / COMPONENT
Insulating glass unit

PURPOSE OF THE TEST
Solar heat gain coefficient (g-value), visible light transmittance, ultraviolet, and infrared light transmittances are measured using an instrument (Window energy profiler "In-frame window tester Model WP4500").

TEST DESCRIPTION
It is determined whether the measured parameters comply with the values specified in the technical specifications of the glass. Measurements are limited to the measuring capabilities of the instrument. Please consult the laboratory for detailed information.

REFERENCE TEST STANDARD
Internal method (TS EN 410-SBG)

INTERNAL TEST METHOD NO
DY.16

TEST REPORT
One test (performance evaluation) report will be issued.

SAMPLE INFORMATION FORM NO
NBF.410

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
On-site

TÜRKAK ACCREDITATION
No

NOTIFIED BODY SCOPE
This test is not conducted within the scope of a notified body under the Construction Products Regulation (305/2011/EU). It is a beneficial test intended for the quality control of insulating glass units.

RECOMMENDED TEST FREQUENCY
Please contact the sales department.


Desiccant – Calcium Chloride (CaCl2) Test

PRODUCT
Insulating glass unit

MATERIAL / COMPONENT TO BE TESTED
Desiccant

PURPOSE OF THE TEST
To determine whether the desiccant used is a genuine desiccant.

DESCRIPTION OF THE TEST
The desiccant is immersed in water, and a soda solution (Na2CO3) is added; if a white precipitate forms, it indicates that calcium chloride (CaCl2) has been added to the desiccant to increase the temperature and irreversibly absorb moisture.

REFERENCE TEST STANDARD
Internal method

INTERNAL TEST METHOD NO
–

TEST REPORT
One test (performance evaluation) report will be issued.

SAMPLE INFORMATION FORM NO.
BF.1279.4(E)

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
Laboratory

TÜRKAK ACCREDITATION
No

NOTIFIED BODY SCOPE
This test is not carried out within the scope of a notified body under the Construction Products Regulation (305/2011/EU). It is a useful test for the quality control of insulating glass units and particularly desiccants.

RECOMMENDED TEST FREQUENCY
Please contact the sales department.


Desiccant – Calcium Oxide (CaO) Test

PRODUCT
Insulating glass unit

MATERIAL / COMPONENT TO BE TESTED
Desiccant

PURPOSE OF THE TEST
To determine whether the desiccant used is a genuine desiccant.

DESCRIPTION OF THE TEST
The desiccant is ground and immersed in water, and the pH value is measured; if the pH is above ten (10), it indicates that quicklime (calcium oxide - CaO) has been added to the desiccant to induce a temperature rise.

REFERENCE TEST STANDARD
Internal method

INTERNAL TEST METHOD NO
–

TEST REPORT
One test (performance evaluation) report will be issued.

SAMPLE INFORMATION FORM NO
NBF.1279.4(E)

LABORATORY SERVICES AGREEMENT
PR.02.ANNEX.1B 'Laboratory Services Agreement' for tests outside the Notified Body scope

TEST LOCATION
Laboratory

TÜRKAK ACCREDITATION
No

NOTIFIED BODY SCOPE
This test is not carried out within the scope of a notified body under the Construction Products Regulation (305/2011/EU). It is a useful test for the quality control of insulating glass units and particularly desiccants.

RECOMMENDED TEST FREQUENCY
Please contact the sales department.